Welcome to SACS Power Pvt. Ltd.....!

200 KVA

200 KVA

Standard scope of supply

Engine with direct injection, water cooled engine, 6 cylinder, in-line, 4 stroke, rated at 1500 RPM, conforming to ISO 3046 / BS 5514 has the following specifications:
  • Mechanical FIP
  • Mechanical governor / Electronic Governor (Optional)
  • Turbocharger, exhaust manifold, stainless steel exhaust flexible connection
  • Radiator cooled with turbocharged after cooled
  • Plate type lube oil cooler
  • Filter –fuel, lube oil
  • Dry type replaceable paper element air cleaner
  • Flywheel housing and flywheel to suit single bearing alternator
  • Starting motor – Electric, battery charging alternator
  • First fill lube oil and coolant

Alternator

Meccalte / (Optional -Stamford/ Crompton Greaves /equivalent)

  • brushless alternator
  • Self-excited, self-regulated
  • Class ‘H’ insulation limited to temperature rise of class H
  • Salient pole revolving field
  • Single bearing
  • Automatic voltage regulator

Acoustic enclosure

Acoustic enclosure – Engine alternator assembly mounted on AVM with Silencer and S.S exhaust bellow suitably optimized to meet stringent sound & emission standards as laid down by MOEF / CPCB

  • Base rail with draw-out type fuel tank is provided with a drain plug, air Vent inlet and outlet connections, level indicator, manhole etc.
  • Sub-base fuel tank with 10 hours capacity.
  • 12 V dry, batteries with connecting leads and terminals.
  • 90% gloss RAL9003 white pure polyester powder coated, base in black colour.

Control panel

RAL 9003 White Powder coated control panel manufactured with CRCA sheet , Control Panel is having following features: -Water and lube oil drain outlets located on the outer surface- Leading to ease of maintenance and cleanliness.

  • MCCB of suitable rating with short circuit protection.
  • Controller which displays voltage, current, KW, PF, Frequency, KWh.
  • Indicating lamps for “Load On” and “Set Running”.
  • Current transformers of suitable ratings
  • Aluminum busbars of suitable capacity with incoming and Outgoing terminations
  • Control fuses duly wired and ferruled

Power cables

Uninyvin copper conductor cables between Alternator & Control panel inside the canopy.

Literature

  • Operation Manual
  • General maintenance & installation Guideline
  • Foundation Drawing
  • Parts manual
  • Generator Controller (GCU 6120-MKII)

    Optional Items

    • Cooling System: Heater Kit for -20 Deg. C Operation / Heater Kit for -30 deg.Cel
    • Electrical Systems: Alternator Space Heater / Higher Rating Battery / Battery Charger / Battery Heater / Copper Bus Bar / Sealable kWh / Earth Fault Relay / Remote Annunciator / Remote monitoring / RTD/BTD Temperature Scanner.
    • AMF &Synchronizing System: AMF panel / AMF with Auto-synchronization (Deep Sea / Woodward)
    • Open Unit (For Export) Exhaust Silencer - Hospital / Residential grade, stainless steel, flexible pipe.
    • Fuel System: Flexible Fuel Lines / SS fuel lines / Fuel Pressure Gauge/ Fuel Flow meter.
    • Enclosed Unit: Sound Enclosure – Super silent / External 990 Lt. Fuel Tank.
    • Miscellaneous: Air Cleaner (Heavy Duty)/Air Cleaner Restriction Indicator Digital / Closed crankcase ventilation